Column Designer
Steel columns to AISC 360-16 and wood columns to NDS 2018, under axial load and bending.
Results
Glulam, LVL and PSL columns are part of Pro. Sawn posts and every steel shape are free.
How the Column Designer Works
The column designer checks one column at a time: a steel W shape, square, rectangular or round Hollow Structural Section (HSS), or pipe to AISC 360-16, or a wood post, glulam, Laminated Veneer Lumber (LVL) or Parallel Strand Lumber (PSL) column to the 2018 National Design Specification for Wood Construction (NDS). Enter the loads at the top of the column by type (dead, live, roof, snow, rain, wind and earthquake) and it builds every ASCE 7-16 load combination, checks each one, and shows the one that governs.
Steel columns (AISC 360-16)
- Compression (Chapter E): flexural buckling about each axis from the effective length KL/r, with the effective width method of section E7 for slender walls and flanges.
- Bending (Chapter F): yielding and lateral-torsional buckling of W shapes about the strong axis, using the weak axis brace spacing as the unbraced length, plus local buckling of HSS walls and flanges.
- Shear (Chapter G) in both directions.
- Axial load and bending together (Chapter H, equations H1-1a and H1-1b), with the moments amplified for the extra bending caused by the axial load (the B1 factor of Appendix 8).
- Both Load and Resistance Factor Design (LRFD) and Allowable Strength Design (ASD).
Wood columns (NDS 2018)
- Compression with the column stability factor CP (section 3.7), from the slenderness le/d about each axis.
- Bending with the beam stability factor CL and, for glulam, the volume factor CV.
- Combined bending and compression (section 3.9.2) and shear (section 3.4.2).
- The load duration factor CD for each combination, and wet service factors for posts outdoors.
- Slenderness le/d is limited to 50.
End conditions
The effective length factor K comes from how the ends are held, using the recommended values from the AISC commentary:
- Pinned top and bottom: K = 1.0
- Fixed base, pinned top: K = 0.8
- Fixed top and bottom: K = 0.65
- Fixed base, free top (a flagpole): K = 2.1. The top can sway, so the designer warns that a frame analysis with second-order (P-Δ) effects may be needed.
Bracing against weak axis buckling splits the height into shorter pieces, each taken as pinned.
Example: a steel column
A W8x31 in A992 steel (Fy = 50 ksi), 12 ft tall and pinned at both ends, carries 20 kips of dead load and 30 kips of live load. With LRFD, 1.2D + 1.6L governs: Pu = 1.2(20) + 1.6(30) = 72 kips.
- Weak axis slenderness: KL/ry = 1.0 × 144 in / 2.02 in = 71.3.
- Elastic buckling stress: Fe = π²E / (KL/r)² = π² × 29,000 / 71.3² = 56.3 ksi.
- Fy/Fe = 0.89, under 2.25, so Fcr = 0.6580.89 × 50 = 34.5 ksi (equation E3-2).
- Pn = FcrAg = 34.5 × 9.12 = 314 kips, and φPn = 0.9 × 314 = 283 kips.
- 72 / 283 = 0.25, so the column passes with plenty of room, and a lighter shape is worth trying.
Example: a wood post
A 6x6 Douglas Fir-Larch No. 2 post indoors, 10 ft tall and pinned at both ends, carries 4 kips dead and 8 kips live. D + L governs at 12 kips, with CD = 1.0.
- Actual stress: fc = 12,000 lb / 30.25 in² = 397 psi.
- Slenderness: le/d = 120 / 5.5 = 21.8, under the limit of 50.
- With Fc = 700 psi and Emin = 470,000 psi, the column stability factor is CP = 0.740.
- Allowable stress: Fc' = 700 × 0.740 = 518 psi.
- 397 / 518 = 0.77, so the post passes.
What it doesn't check
- Connections, base plates and anchor bolts. The anchor bolt designer covers the anchors.
- Tension in wood columns under uplift. The designer flags it when a combination pulls on the column.
- The frame the column is part of. For a column in a moment frame, get the forces from a frame analysis such as the frame designer.
- Fire, corrosion and decay.
The results are a design aid. Have a licensed engineer check a design before it's built.
Frequently asked questions
How much load can a steel column carry?
It depends mostly on the shape and its height. Buckling about the weak axis usually governs, so a taller column carries much less. A 12 ft W8x31 in A992 steel carries 283 kips with LRFD. The steel column design examples work through more cases.
How much load can a 6x6 post carry?
A 10 ft Douglas Fir-Larch No. 2 6x6 indoors carries about 15,700 lb of dead plus live load (518 psi × 30.25 in²). A taller post carries less: its stability factor drops as le/d grows.
What K factor should I use?
Use K = 1.0 for a column pinned at both ends, which suits most building columns with simple beam connections and braced frames. Use 2.1 for a column fixed at the base and free at the top.
Is the column designer free?
Yes. Steel columns and sawn wood posts are free without an account. Pro adds glulam, LVL and PSL columns, saved columns and PDF reports.